Description
The UD-2000 Digital Alarm Communicator Transmitter (DACT) provides for up to two (2) phone lines for communication to a monitoring station. The UD-2000 communicates using the SIADCS or Ademco Contact ID protocols. When enabled, the DACT automatically monitors each phone line or voltage and has the ability to seize the line and connect with a remote receiver. Once the communication is complete, the DACT will hang up.
Features:
- Allows for communication to Monitoring Station
- Communicates using SIA-DCS or Ademco Contact ID Protocols
- For use with IPA, AFC, and ARC series Addressable Panels and PFC-4064 Conventional Panel
- Status LEDs indicate operation of DACT card
- Installs with ease behind main panel LCD display via User Interface bracket
- Device address is set internally to address 1
Technical Specifcations
Voltage
22.0-24.0V
Current
- Standby - 16mA
- Alarm - 23mA
Operating Temperature
0°C - 49°C (32°F- 120°F)
Operating Humidity
10% - 93% @ 30°C (86°F) (non-condensing)
Mount Type
In FACP Behind keypad
Compliance
- FM
- UL Listed