in stock

Potter Electric Signal

SKU IDC-6 IDC-6

Initiating Device Circuit Expander - IDC-6

Product Rating Product Rating Product Rating Product Rating Product Rating 0 Reviews
Write a Review
Price:
$547.00
  • Weight:
    1.90 LBS
  • Shipping:
    Calculated at Checkout

Key features

Input Zone Wiring Resistance 100 ohms max
Input Zone Short Circuit Current 47 mA
Operating Temperature 32° to 120°F (0° to 49° C)
Operating Humidity 10%-93% (non-condensing)
Compliance UL Listed
Sale assistant
Contact our Sales Team for a tailored experience
Adding to cart… The item has been added
?Special Order Information
Sign In for Dealer Pricing Become a BLVS Customer

Description

The Initiating Device Circuit Expander (IDC-6) provides an additional 6 inputs per module. The panel supports up to thirty-one (31) IDC-6 modules. The circuits are power-limited and supervised. All inputs are suitable to monitor 2-wire smoke detectors. Smoke detectors shall be installed in compliance with NFPA 72. Inputs can also be used for automatic, manual, waterflow or supervisory service. The IDC-6 communicates via the PLink communication bus. The IDC-6 can be mounted in either the control panel cabinet, the intelligent power supply, AE-2, AE-8 or the AE-14 expander cabinet. Each card is mounted to the exclusive Stacker Bracket for secure and accessible mounting.

Features:

  • Mounts with included stacker bracket
  • May mount in panel, accessory cabinet, AE-2, AE-8 or AE-14 Accessory Cabinets or the PSN-1000/E Power Supply
  • Provides 6 IDC Input Circuits
  • Maximum 31 IDC-6 per panel
  • Maximum P-Link wire length of 20 feet

Technical Specifcations

Current
  • Stnadby - 20 mA
  • Alarm - 20 mA
Input Zone Wiring Resistance
100 ohms max
Input Zone Short Circuit Current
47 mA
Operating Temperature
32° to 120°F (0° to 49° C)
Operating Humidity
10%-93% (non-condensing)
Compliance
UL Listed

Datasheet