Description
The Initiating Device Circuit Expander (IDC-6) provides an additional 6 inputs per module. The panel supports up to thirty-one (31) IDC-6 modules. The circuits are power-limited and supervised. All inputs are suitable to monitor 2-wire smoke detectors. Smoke detectors shall be installed in compliance with NFPA 72. Inputs can also be used for automatic, manual, waterflow or supervisory service. The IDC-6 communicates via the PLink communication bus. The IDC-6 can be mounted in either the control panel cabinet, the intelligent power supply, AE-2, AE-8 or the AE-14 expander cabinet. Each card is mounted to the exclusive Stacker Bracket for secure and accessible mounting.
Features:
- Mounts with included stacker bracket
- May mount in panel, accessory cabinet, AE-2, AE-8 or AE-14 Accessory Cabinets or the PSN-1000/E Power Supply
- Provides 6 IDC Input Circuits
- Maximum 31 IDC-6 per panel
- Maximum P-Link wire length of 20 feet
Technical Specifications
Current
- Stnadby - 20 mA
- Alarm - 20 mA
Input Zone Wiring Resistance
100 ohms max
Input Zone Short Circuit Current
47 mA
Operating Temperature
32° to 120°F (0° to 49° C)
Operating Humidity
10%-93% (non-condensing)
Compliance
UL Listed