Description
The AFC-1000 is an expandable analog/addressable releasing fire alarm system with a total system capacity of 1270 addresses. Additional capacity on the system is achieved using multi-point SLC modules The control panel utilizes the exclusive Potter protocol that includes a complete line of sensors and modules. The system is expandable with a total of nine additional addressable Signaling Line Circuits (SLC) each with a maximum of 127 devices. Each SLC may be comprised of any combination of smoke sensor, heat detectors or modules and allows for a total of 50 ohms of impedance and may use any wire compliant with the National Electrical Code (NEC).
Features:
- 1,270 addresses available on this analog addressable system
- 4 Input/Output (I/O) Circuits for system flexibility rated at 1 Amp each
- Strobe Synchronization and System Wide Sync for Gentex®, AMSECO®, Cooper Wheelock® and System Sensor® strobes
- 4,000 Event History Buffer
- Built in IP communicator
- Ethernet Port for Programming and Network Connectivity
Technical Specifications
Current
Standby:-130 mA Alarm:220 mA
Operating Temperature
32° to 120° (0°C to 49°C)
Operating Humidity
93% non-condensing
Color
Red
Voltage
5.0 Amps @ 120 VAC 50/60 HZ 3.0 Amps @ 240 VAC 50/60 HZ
Warranty
5 Years Warranty
Warranty
5 Years Warranty