Description
Construction:
Genesis® Plenum Rated Unshielded Multiconductor Cable features the following quality and convenience characteristics:
- Bare Copper conductors for excellent conductivity and low voltage drop.
- Low-Smoke PVC insulation.
- Plenum PVC jacket.
- Durable rip cord for efficient jacket stripping and removal.
- Countdown® Length Markings for easy tracking of usage and remaining cable. Speed Bag variations use sequential length markings.
- Rated for 300 Volts
- Rated for -20 °C to 75 °C.
Standards & References:
Genesis® Plenum Rated Unshielded Multiconductor Cable meets or exceeds the following:
- NFPA 262 - Plenum Rated
- CSA C22.2 No. 2556 - FT6 Rated
- UL 444 - Communication Cables, Type CMP (22 AWG - 16 AWG)
- UL 1424 - Cables for Power-Limited Fire-Alarm Circuits, Type FPLP
- UL 13 - Power-Limited Circuit Cables, Type CL3P
- REACH/RoHS Compliant
Application & Features:
Genesis® Plenum Rated Unshielded Multiconductor Cable is suitable for installation as follows:
- In fabricated ducts as described in NEC 300.22(B).
- In other spaces used for environmental air as described in NEC 300.22(C).
- In risers.
- Within buildings in other than air-handling spaces and risers.