Description
The PAD200-DUCTR is designed and built to meet all local requirements, as well as the NFPA regulations regarding duct smoke detectors. Air sampling is accomplished by two tubes which protrude into the duct. An exhaust tube of one standard length (7-Inch) is supplied in the installation kit with the smoke duct unit. Once the duct width has been determined the air intake sampling tubes must be ordered. Sampling tubes are supplied in three standard lengths: 2.5 ft., 5 ft., and 10 ft. and cut to size to fit the duct.
Features:
- Detects smoke in building HVAC ducts
- Ships complete with housing and head
- No screens or filters in housing
- Durable plastic enclosure and clear cover
- Utilizes simple snap in sampling tubes STN series
- One form C relay
Technical Specifcations
Voltage
24 VDC
Current
500 µA
Air Velocity
100 to 4000 ft./min
Operating Temperature
32°F to 120°F (0°C to 49°C)
Operating Humidity
10% to 85% Relative Humidity (non- condensing)
Material
- Plastic backbox
- clear plastic cover
Finish
Gray backbox with clear cover
Compliance
- UL Listed
- UUKL Listed
Warranty
5 Years Warranty
Warranty
5 Years Warranty